Spezial-PVC control cable with
oil resistant outer sheath adapted to
DIN VDE 0285-525-2-51 /
DIN EN 50525-2-51 and IEC 60227/75
deviation of conductor cross sections
Temperature range
flexing -5°C to +70°C
fixed installation -40°C to +70°C
Nominal voltage U0/U 300/500 V
Test voltage 2 kV, 5 minutes
Breakdown voltage min. 4000 V
Insulation resistance
min. 20 MOhm x km
Minimum bending radius
flexing 7,5x cable Ø
fixed installation 4x cable Ø
Radiation resistance
up to 80x106 cJ/kg (up to 80 Mrad)
Bare copper conductor, to
DIN VDE 0295 cl.5, fine wire,
BS 6360 cl.5, IEC 60228 cl.5
Core insulation of special PVC
compound type TI2 to
DIN VDE 0207-363-3 / DIN EN 50363-3
Core identification to DIN VDE 0293
black cores with continuous white
numbering
GN-YE conductor, 3 cores and above
in the outer layer
Cores stranded in layers with
optimal lay length
Outer sheath of special PVC
compound type TM5 to
DIN VDE 0207-363-4-1/DIN EN 50363-4-1
Sheath colour: grey (RAL 7001)
With meter marking
G = with GN-YE conductor
x = without GN-YE conductor (OZ)
AWG sizes are approximate equivalent
values. The actual cross section is in mm².
Screened analogue type:
(H)05VVC4V5-K