TRAYCONTROL® 300
flexible, oil resistant, NFPA 79
Cable structure
Tinned copper conductor, fine wire
with AWG dimensions
Core insulation of special PVC
(AWG 22 -AWG 16 with transparent
nylon skin)
Core identification to international
colour code
Cores stranded in layers with
optimal lay length
Separator
Outer sheath of special PVC
Sheath colour: grey (RAL 7001)
With length marking in feet
Properties
The materials used during manufacturing
are cadmium-free, contain no silicone
and are free from substances harmful
to the wetting properties of lacquers
Tests
Self-extinguishing and flame retardant
acc. to CSA FT4
UL (AWG 22 - AWG 16):
PLTC-ER, ITC-ER, Type CM, NFPA 79,
OIL RES I & II, Class I Div. 2,
NEC Art. 501, 725, 760 & 800, AWM 2517
UL (AWG 24 - AWG 28):
CM, AWM 2517, rated OIL RES I & II,
NEC Art. 725, 760 & 800, NFPA 79
CSA:
CSA CMG FT4, AWM I/II A/B FT4
Note
Advantages
Highly flexible easy to install
Oil resistant to OIL RES I & II
Available on request
PUR or TPE outer sheath
Sheath colour to suit customer
requirements
Technical data
Flexible PVC data and control cable
Temperature range
-25°C to +105°C
Nominal voltage
300 V
Test voltage
2000 V
Minimum bending radius
flexing 6x cable Ø
Radiation resistance
up to 80x106 cJ/kg (up to 80 Mrad)